Loading Circuit Breaker Detail

KD2225 Eaton / Cutler-Hammer / Westinghouse Molded Case Circuit Breakers

Item # KD2225

NOTE: Images are for Reference Only

Product Specifications

Type
KD
Amperage
225
Poles
2
Voltage
600

KD2225 Description

SERIES C K-FRAME MOLDED CASE CIRCUIT BREAKER 2P 225A CB Molded Case Circuit Breakers from Eaton / Cutler-Hammer / Westinghouse

Features and Benefits

Additional Information:
Interchangeable Trip Circuit Breaker; Type Thermal Magnetic, Standard Interrupting Capacity, Molded Case; Frame Type KD; Voltage Rating 600 Volt AC 50/60 Hertz, 250 Volt DC; Maximum AC Voltage Rating 600 Volt; Maximum DC Voltage Rating 250 Volt; Current Rating 225 Amp at 40 Deg C; Number of Poles 2; Interrupting Rating 65 Kiloamp at 240 Volt AC, 35 Kiloamp at 480 Volt AC, 25 Kiloamp at 600 Volt AC, 10 Kiloamp at 250 Volt DC (NEMA/UL/CSA), 65 Kiloamp at 240 Volt AC, 40 Kiloamp at 380/415 Volt AC, 10 Kiloamp at 250 Volt DC (IEC); Terminal Type Aluminum Line and Load; Size 5.5 Inch Width x 4.1 Inch Depth x 10.13 Inch Height; Approval UL 489, CSA C22.2; Application HACR; Applicable Standard IEC 60947-2, SABS 156, SEV 157-1, NFC 63-120, VDE0660, Federal Specification W-C-375b 23a